{"id":3129,"date":"2020-06-15T20:42:08","date_gmt":"2020-06-15T17:42:08","guid":{"rendered":"https:\/\/www.medibim.com.tr\/TR\/?p=3129"},"modified":"2025-04-18T11:06:26","modified_gmt":"2025-04-18T08:06:26","slug":"hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi","status":"publish","type":"post","link":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/","title":{"rendered":"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131"},"content":{"rendered":"\n<h1><span style=\"font-size: 14pt;\">Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131<\/span><\/h1>\n<p>[rml_read_more]<\/p>\n<p>Hepa filtre ka\u00e7ak testi ISO 14644 standart\u0131na g\u00f6re 2 farkl\u0131 y\u00f6ntemle yap\u0131lmaktad\u0131r. Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 i\u00e7in kullan\u0131lan bu 2 y\u00f6ntem;\u00a0 k\u0131saca Fotometre tekni\u011fi ve Partik\u00fcl Say\u0131m (OPC ya da DPC) tekni\u011fi olarak belirlenebilir.<\/p>\n<p>\u0130la\u00e7, t\u0131bbi cihaz, sa\u011fl\u0131k, g\u0131da, havac\u0131l\u0131k, yar\u0131 iletken, mikroelektronik ve s\u00fcrekli artan say\u0131da farkl\u0131 sekt\u00f6rdeki temiz oda ortamlar\u0131n\u0131n periyodik validasyonu ISO 14644 standard\u0131 ile uluslararas\u0131 olarak d\u00fczenlenmektedir.<br \/>Bu uluslararas\u0131 standart bir dizi d\u00fcnya standartlar\u0131n\u0131 uyumlu hale getirdi\u011fi i\u00e7in devlet \u00e7\u0131karlar\u0131 dikkate al\u0131nm\u0131\u015ft\u0131r.<\/p>\n<p>Bu sebeple validasyon y\u00f6ntemleri partik\u00fcl say\u0131c\u0131\/diluter veya aerosol fotometre olmak \u00fczere 2 farkl\u0131 \u015fekilde uygulanmaktad\u0131r.<\/p>\n<p><span style=\"font-size: 12pt;\">Bu yaz\u0131, <\/span><span style=\"font-size: 12pt;\">Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 yapmak bak\u0131m\u0131ndan ve bilgi vermek amac\u0131yla d\u00fczenlenmi\u015ftir.<\/span><\/p>\n<h2><span style=\"font-size: 12pt;\">Bahsi ge\u00e7en 2 Y\u00f6ntem Kar\u015f\u0131la\u015ft\u0131r\u0131labilir mi ?<\/span><\/h2>\n<p>Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 kapsam\u0131nda \u00f6nemli bir sorun, tak\u0131l\u0131 filtre ka\u00e7ak testini ger\u00e7ekle\u015ftirmek i\u00e7in optik partik\u00fcl saya\u00e7lar\u0131n\u0131n veya aerosol fotometrelerin iste\u011fe ba\u011fl\u0131 uygulamas\u0131 ile ilgilidir. ISO 14644-3 (B.6.1.1) standart\u0131 bile bu iki y\u00f6ntemle elde edilen test sonu\u00e7lar\u0131n\u0131n do\u011frudan kar\u015f\u0131la\u015ft\u0131r\u0131labilir olmad\u0131\u011f\u0131n\u0131 belirtmektedir.<\/p>\n<p>Buna ra\u011fmen bir y\u00f6ntem belirlemek bak\u0131m\u0131ndan birisi se\u00e7ilmelidir.\u00a0<span style=\"font-size: 12pt;\">Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 bu konuda ayd\u0131nlat\u0131c\u0131 olacakt\u0131r.<\/span><\/p>\n<h2><span style=\"font-size: 12pt;\">\u00dclke bazl\u0131 reg\u00fclasyonlar\u0131n etkisi:<\/span><\/h2>\n<p>Eski ABD FED-STD-209E fotometreleri temel al\u0131narak ABD ve \u0130ngiltere b\u00f6lgesinde tipik olarak ilk tercihtir.Alman VDI 2083 d\u00fczenlemeleri nedeniyle Almanya ve Avrupa \u00fclkelerinin \u00e7o\u011funda standart optik partik\u00fcl saya\u00e7lar\u0131 tercih edilmektedir.<\/p>\n<p>\u015eimdiye kadar, iki \u00f6l\u00e7\u00fcm y\u00f6nteminden sadece birini referans olarak belirleyen hi\u00e7bir uluslararas\u0131 anla\u015fma bulunamam\u0131\u015ft\u0131r.ABD FED-STD-209E 2001 y\u0131l\u0131nda tekrar iptal edilirken, bu anla\u015fmazl\u0131k nedeniyle federal VDI 2083 standard\u0131 hala aktiftir.<\/p>\n<h2><span style=\"font-size: 12pt;\">ISO-14644 standart\u0131 do\u011frultusunda Validasyon Test Prosed\u00fcrleri<\/span><\/h2>\n<p>Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 kapsam\u0131nda a\u015fa\u011f\u0131daki tablo, \u00f6zellikle oda s\u0131n\u0131fland\u0131rmas\u0131, filtre s\u0131z\u0131nt\u0131 testi ve geri kazan\u0131m testi i\u00e7in kullan\u0131lacak \u00f6l\u00e7\u00fcm y\u00f6ntemine odaklanarak ISO 14644 taraf\u0131ndan gerekli ve iste\u011fe ba\u011fl\u0131 olarak temiz oda testlerini g\u00f6stermektedir.<br \/>Optik partik\u00fcl sayac\u0131, gerekli oda s\u0131n\u0131fland\u0131rmas\u0131n\u0131n ve iste\u011fe ba\u011fl\u0131 geri kazan\u0131m testinin ger\u00e7ekle\u015ftirilmesi i\u00e7in zorunlu oldu\u011fundan, bu optik partik\u00fcl sayac\u0131n\u0131n fotometre anla\u015fmazl\u0131\u011f\u0131na kar\u015f\u0131 yaln\u0131zca iste\u011fe ba\u011fl\u0131 filtre s\u0131z\u0131nt\u0131 testi ile ilgili oldu\u011fu g\u00f6sterilmi\u015ftir.<br \/>Bu, zorunlu oda s\u0131n\u0131fland\u0131rmas\u0131 ve iste\u011fe ba\u011fl\u0131 kurtarma testi temiz oda do\u011frulama prosed\u00fcr\u00fcn\u00fcn bir fotometre kullan\u0131larak yap\u0131lamayaca\u011f\u0131 anlam\u0131na gelir.<\/p>\n<h2><span style=\"font-size: 12pt;\">Metod Tablosu<\/span><\/h2>\n<table>\n<tbody>\n<tr>\n<td width=\"75\">\n<p>\u00a0<\/p>\n<\/td>\n<td width=\"302\">\n<p>TEST<\/p>\n<\/td>\n<td width=\"76\">\n<p>REFERANS C\u0130HAZ<\/p>\n<\/td>\n<td width=\"151\">\n<p>\u00d6L\u00c7\u00dcM METODU<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"75\">\n<p>Zorunlu<\/p>\n<\/td>\n<td width=\"302\">\n<p>Airborne particle count for\u00a0 classification and test measurement of cleanrooms and clean air devices<\/p>\n<\/td>\n<td width=\"76\">\n<p>C.1<\/p>\n<\/td>\n<td width=\"151\">\n<p>PART\u0130K\u00dcL SAYICI<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"75\">\n<p>Opsiyonel<\/p>\n<\/td>\n<td width=\"302\">\n<p>Installed filter system leakage test<\/p>\n<\/td>\n<td width=\"76\">\n<p>C.6<\/p>\n<\/td>\n<td width=\"151\">\n<p>C.6.1 FOTOMETRE<\/p>\n<p>C.6.2 PART\u0130K\u00dcL SAYICI<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"75\">\n<p>Opsiyonel<\/p>\n<\/td>\n<td width=\"302\">\n<p>Recovery Test<\/p>\n<\/td>\n<td width=\"76\">\n<p>C.12<\/p>\n<\/td>\n<td width=\"151\">\n<p>PART\u0130K\u00dcL SAYICI<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>\u00a0<\/p>\n<figure id=\"attachment_3131\" aria-describedby=\"caption-attachment-3131\" style=\"width: 614px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-3131 size-full\" src=\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2020\/06\/resim-1.jpg\" alt=\"Hepa Upstream Downstream\" width=\"614\" height=\"291\" srcset=\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2020\/06\/resim-1.jpg 614w, https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2020\/06\/resim-1-300x142.jpg 300w\" sizes=\"auto, (max-width: 614px) 100vw, 614px\" \/><figcaption id=\"caption-attachment-3131\" class=\"wp-caption-text\">Hepa Upstream Downstream<\/figcaption><\/figure>\n<h2><span style=\"font-size: 12pt;\"><strong>Montaj\u0131 Yap\u0131lm\u0131\u015f Kurulu Filtre Ka\u00e7ak Testi<\/strong><\/span><\/h2>\n<p>Kurulu y\u00fcksek verimli bir partik\u00fcl hava filtresini (HEPA, ULPA) test etmek i\u00e7in, filtrenin yukar\u0131s\u0131nda uygun bir test aerosol\u00fc olu\u015fturulmal\u0131d\u0131r. Bu test aerosol\u00fcn\u00fcn partik\u00fcl boyutu da\u011f\u0131l\u0131m\u0131, test edilen filtrenin MPPS aral\u0131\u011f\u0131nda olmal\u0131d\u0131r. Bir yukar\u0131 ve a\u015fa\u011f\u0131 ak\u0131\u015f partik\u00fcl konsantrasyonu \u00f6l\u00e7\u00fcm\u00fc yap\u0131larak, kurulu filtrenin herhangi bir s\u0131z\u0131nt\u0131s\u0131n\u0131 bulmak i\u00e7in lokal partik\u00fcl penetrasyonu belirlenir.<\/p>\n<h2><span style=\"font-size: 12pt;\"><strong>\u00d6l\u00e7\u00fcm Prensipleri<\/strong><\/span><\/h2>\n<p>Optik partik\u00fcl say\u0131m cihazlar\u0131 lazer \u0131\u015f\u0131\u011f\u0131 sa\u00e7\u0131lma \u00f6l\u00e7\u00fcmlerine dayanmaktad\u0131r. Odaklanm\u0131\u015f lazer \u0131\u015f\u0131n\u0131 kullanarak partik\u00fcller tek tek analiz edilir. Bu nedenle partik\u00fcl say\u0131s\u0131 konsantrasyonlar\u0131 elde edilir. Tek partik\u00fcl impulslar\u0131 genlik boyutuna g\u00f6re s\u0131n\u0131fland\u0131r\u0131ld\u0131\u011f\u0131ndan, \u00f6l\u00e7\u00fclen her partik\u00fcl hakk\u0131nda bilgi ek olarak elde edilebilir. ISO 14644&#8217;ten, kullan\u0131lan optik partik\u00fcl sayac\u0131nda a\u015fa\u011f\u0131daki minimum gereksinimler vard\u0131r:<br \/><br \/><\/p>\n<table>\n<tbody>\n<tr>\n<td width=\"298\">\n<p><strong>A\u00e7\u0131klama<\/strong><\/p>\n<\/td>\n<td width=\"298\">\n<p><strong>Teknik \u00d6zellik<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"298\">\n<p>Partik\u00fcl Boyut Aral\u0131k<\/p>\n<\/td>\n<td width=\"298\">\n<p>0.1 \u2013 5 \u03bcm<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"298\">\n<p>Boyut \u00e7\u00f6z\u00fcn\u00fcrl\u00fc\u011f\u00fc<\/p>\n<\/td>\n<td width=\"298\">\n<p>&lt; %10<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"298\">\n<p>Say\u0131m verimlili\u011fi<\/p>\n<\/td>\n<td width=\"298\">\n<p>%50 at maks\/min partik\u00fcl boyutu<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"298\">\n<p>D\u00fc\u015f\u00fck partik\u00fcl say\u0131s\u0131 konsantrasyonu<\/p>\n<\/td>\n<td width=\"298\">\n<p>&lt; 1 \/ 5dakika \u00a0( 5 dakikada 1 den az)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"298\">\n<p>Y\u00fcksel partik\u00fcl say\u0131s\u0131 konsantrasyonu<\/p>\n<\/td>\n<td width=\"298\">\n<p>%75 belirlenen konsantrasyonda<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"298\">\n<p>\u00d6l\u00e7\u00fcm Belirsizli\u011fi<\/p>\n<\/td>\n<td width=\"298\">\n<p>\u00b1 %20 ayarlanan boyutta konsantrasyon hatas\u0131<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Optik partik\u00fcl sayac\u0131 taraf\u0131ndan monte edilmi\u015f bir filtre s\u0131zd\u0131rmazl\u0131k testi ger\u00e7ekle\u015ftirmek i\u00e7in tipik olarak bir test aerosol\u00fc olarak DEHS veya PAO kullan\u0131l\u0131r. Ak\u0131\u015f yukar\u0131 partik\u00fcl \u00f6l\u00e7\u00fcmleri i\u00e7in, optik partik\u00fcl sayac\u0131nda rastlant\u0131 hatalar\u0131n\u0131 \u00f6nlemek i\u00e7in bir aerosol seyreltme sistemi uygulanmal\u0131d\u0131r.<\/p>\n<p>Ak\u0131\u015f a\u015fa\u011f\u0131 partik\u00fcl say\u0131s\u0131 konsantrasyonu bir seyreltme sistemi olmadan \u00f6l\u00e7\u00fcl\u00fcr. Genel olarak \u00f6l\u00e7\u00fcmler, iki \u00f6zde\u015f optik partik\u00fcl sayac\u0131yla e\u015fzamanl\u0131 olarak veya daha sonra yukar\u0131 ve a\u015fa\u011f\u0131 ak\u0131\u015f \u00f6rneklemesi de\u011fi\u015ftirilerek bir saya\u00e7 ile ger\u00e7ekle\u015ftirilebilir.<\/p>\n<h2><span style=\"font-size: 12pt;\">S\u0131z\u0131nt\u0131 Do\u011frulamas\u0131<\/span><\/h2>\n<p>S\u0131z\u0131nt\u0131 do\u011frulamas\u0131 i\u00e7in t\u00fcm filtre kesiti, yakla\u015f\u0131k 5 cm \/ s&#8217;lik bir izokinetik \u00f6rnekleme probu ile taran\u0131r. Bu tarama s\u0131ras\u0131nda potansiyel ka\u00e7aklar\u0131n bulunmas\u0131 durumunda, bir ka\u00e7ak durumunu \/ ka\u00e7ak durumunu do\u011frulamak i\u00e7in bu potansiyel ka\u00e7ak konumlar\u0131nda sabit bir 1 dakikal\u0131k \u00f6l\u00e7\u00fcm ger\u00e7ekle\u015ftirilmelidir.<\/p>\n<p>Gerekli yukar\u0131 ak\u0131\u015f partik\u00fcl say\u0131s\u0131 konsantrasyonunun ayarlanmas\u0131, ISO 14644-3 B 6.3.3&#8217;te a\u00e7\u0131klanmaktad\u0131r. Makul a\u015fa\u011f\u0131 ak\u0131\u015f tarama h\u0131zlar\u0131n\u0131n ger\u00e7ekle\u015ftirilebilece\u011fi \u015fekilde se\u00e7ilmelidir.<\/p>\n<p>Bir optik partik\u00fcl sayac\u0131 (1 cfm) ile farkl\u0131 filtre s\u0131n\u0131flar\u0131n\u0131 test etmek i\u00e7in yukar\u0131 ak\u0131\u015f partik\u00fcl say\u0131s\u0131 konsantrasyonlar\u0131 i\u00e7in tipik ayarlar, a\u015fa\u011f\u0131daki tabloda \u00f6rnek olarak g\u00f6sterilmektedir.<\/p>\n<table width=\"612\">\n<tbody>\n<tr>\n<td rowspan=\"2\" width=\"122\">\n<p><strong>Filtre S\u0131n\u0131f\u0131<\/strong><\/p>\n<\/td>\n<td width=\"122\">\n<p><strong>Upstream Partik\u00fcl Say\u0131m Konsantrasyonu<\/strong><\/p>\n<\/td>\n<td width=\"122\">\n<p><strong>Nominal Verimlilik<\/strong><\/p>\n<\/td>\n<td colspan=\"2\" width=\"245\">\n<p><strong>Downstream Partik\u00fcl Say\u0131m Konsantrastonu<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"122\">\n<p><strong>[1\/cm3]<\/strong><\/p>\n<\/td>\n<td width=\"122\">\n<p><strong>[%]<\/strong><\/p>\n<\/td>\n<td width=\"122\">\n<p><strong>[1\/cm3]<\/strong><\/p>\n<\/td>\n<td width=\"122\">\n<p><strong>[1\/s]<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"122\">\n<p>H13<\/p>\n<\/td>\n<td width=\"122\">\n<p>100<\/p>\n<\/td>\n<td width=\"122\">\n<p>99,95<\/p>\n<\/td>\n<td width=\"122\">\n<p>0,05<\/p>\n<\/td>\n<td width=\"122\">\n<p>24<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"122\">\n<p>H14<\/p>\n<\/td>\n<td width=\"122\">\n<p>1.000<\/p>\n<\/td>\n<td width=\"122\">\n<p>99,995<\/p>\n<\/td>\n<td width=\"122\">\n<p>0,05<\/p>\n<\/td>\n<td width=\"122\">\n<p>24<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"122\">\n<p>U15<\/p>\n<\/td>\n<td width=\"122\">\n<p>10.000<\/p>\n<\/td>\n<td width=\"122\">\n<p>99,9995<\/p>\n<\/td>\n<td width=\"122\">\n<p>0,05<\/p>\n<\/td>\n<td width=\"122\">\n<p>24<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>\u00a0<\/p>\n<p><strong>Fotometreler<\/strong> esas olarak iletim \u00f6l\u00e7\u00fcmlerine dayan\u0131r, baz\u0131 durumlarda ileri sa\u00e7\u0131lma uygulan\u0131r. Par\u00e7ac\u0131k kolektifleri g\u00f6zlendi\u011finde, ortalama par\u00e7ac\u0131k boyutunun yan\u0131 s\u0131ra par\u00e7ac\u0131k k\u00fctle konsantrasyonlar\u0131 da olu\u015fur. Partik\u00fcl boyutu da\u011f\u0131l\u0131m\u0131 hakk\u0131nda bilgi elde edilemez. ISO 14644&#8217;ten, kullan\u0131lan fotometrede a\u015fa\u011f\u0131daki minimum gereksinimler vard\u0131r:<\/p>\n<table width=\"609\">\n<tbody>\n<tr>\n<td width=\"305\">\n<p><strong>A\u00e7\u0131klama<\/strong><\/p>\n<\/td>\n<td width=\"305\">\n<p><strong>\u00d6zellik<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"305\">\n<p>Partik\u00fcl K\u00fctle konsantrasyonu<\/p>\n<\/td>\n<td width=\"305\">\n<p>0,001 \u03bcg\/l \u2026 100 \u03bcg\/l<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"305\">\n<p>Konsantrasyon \u00c7\u00f6z\u00fcn\u00fcrl\u00fc\u011f\u00fc<\/p>\n<\/td>\n<td width=\"305\">\n<p>0,001 \u03bcg\/l<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"305\">\n<p>Partik\u00fcl boyut aral\u0131k<\/p>\n<\/td>\n<td width=\"305\">\n<p>0,1 \u2026 0,6 \u03bcm<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"305\">\n<p>\u00d6l\u00e7\u00fcm belirsizli\u011fi<\/p>\n<\/td>\n<td width=\"305\">\n<p>\u00b15%<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Bir aerosol fotometre ile kurulu bir filtre s\u0131z\u0131nt\u0131 testi ger\u00e7ekle\u015ftirmek i\u00e7in tipik olarak bir test aerosol\u00fc olarak DOP kullan\u0131l\u0131r. Ancak bu DOP&#8217;nin Avrupa d\u00fczenlemeleri (EN 1272\/2008) i\u00e7in tehlikeli oldu\u011fu d\u00fc\u015f\u00fcn\u00fclmektedir. S\u0131z\u0131nt\u0131 do\u011frulama, t\u00fcm filtre kesitinin taranmas\u0131yla da yap\u0131l\u0131r. Standart taraf\u0131ndan 20\u2026 80 mg \/ m\u00b3 aras\u0131nda bir yukar\u0131 ak\u0131\u015f k\u00fctle konsantrasyonu \u00f6nerilir. 0,5 \u03bcm modal partik\u00fcl boyutuna ve 0,98 g \/ cm\u00b3 de\u011ferine sahip bir test aerosol\u00fc varsayarsak, bu, optik partik\u00fcl sayac\u0131 \u00f6l\u00e7\u00fcmlerine k\u0131yasla yakla\u015f\u0131k 1000 kat daha y\u00fcksek olan yakla\u015f\u0131k 160.000\u2026 650.000 1 \/ cm\u00b3 partik\u00fcl say\u0131s\u0131 konsantrasyonuyla ilgilidir (ayr\u0131ca ISO 14644-3 B.6.1.2&#8217;ye bak\u0131n\u0131z).<\/p>\n<h2><span style=\"font-size: 12pt;\"><strong>Her \u0130ki \u00d6l\u00e7\u00fcm Metodunun Kar\u015f\u0131la\u015ft\u0131rmas\u0131<\/strong><\/span><\/h2>\n<p>Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 i\u00e7in test y\u00f6ntemi olarak bir optik partik\u00fcl sayac\u0131 ve bir fotometre kullanman\u0131n s\u0131z\u0131nt\u0131 testi sonu\u00e7lar\u0131 do\u011frudan kar\u015f\u0131la\u015ft\u0131r\u0131lamaz. Bunun nedeni, bir par\u00e7ac\u0131k sayac\u0131n\u0131n par\u00e7ac\u0131k say\u0131s\u0131 konsantrasyonlar\u0131n\u0131n do\u011frudan bir fotometrenin par\u00e7ac\u0131k k\u00fctle konsantrasyonlar\u0131 ile kar\u015f\u0131la\u015ft\u0131r\u0131lamamas\u0131ndan kaynaklanmaktad\u0131r.<\/p>\n<p>Partik\u00fcl say\u0131s\u0131 konsantrasyonlar\u0131nda k\u00fc\u00e7\u00fck partik\u00fcller g\u00fc\u00e7l\u00fc say\u0131m etkileri g\u00f6sterir, partik\u00fcl k\u00fctle konsantrasyonlar\u0131nda b\u00fcy\u00fck partik\u00fcller bask\u0131nd\u0131r. Tek bir par\u00e7ac\u0131k analizi uygulanarak par\u00e7ac\u0131k saya\u00e7lar\u0131 \u00f6zellikle k\u00fc\u00e7\u00fck par\u00e7ac\u0131k konsantrasyonlar\u0131n\u0131 \u00f6l\u00e7mek i\u00e7in tasarlanm\u0131\u015ft\u0131r. Bu nedenle ak\u0131\u015f yukar\u0131 aerosol seyreltme gereklidir.<\/p>\n<p>Piyasada bir dizi uygun seyreltme sistemi bulunmaktad\u0131r.<\/p>\n<h2><span style=\"font-size: 12pt;\">Fotometreler <\/span><\/h2>\n<p>Fotometreler par\u00e7ac\u0131k kolektifleri g\u00f6zlendi\u011finden \u00f6zellikle y\u00fcksek konsantrasyonlar\u0131 \u00f6l\u00e7mek i\u00e7in uygundur. \u00d6zellikle y\u00fcksek verimli filtrelerde yeterli bir a\u015fa\u011f\u0131 ak\u0131\u015f k\u00fctle konsantrasyonuna ula\u015fmak i\u00e7in, fotometre \u00f6l\u00e7\u00fcmlerinde \u00e7ok y\u00fcksek bir yukar\u0131 ak\u0131\u015f konsantrasyonu gereklidir. Bu y\u00fcksek ak\u0131\u015f yukar\u0131 konsantrasyonu filtre kontaminasyonu ile sonu\u00e7land\u0131\u011f\u0131ndan ISO 14644-3 B.6.1.2c, bir fotometre testinin sadece filtreden \u00e7\u0131kan test aerosol\u00fcn\u00fcn operasyondaki temiz oda i\u00e7indeki \u00fcr\u00fcnler veya personel i\u00e7in kritik olmad\u0131\u011f\u0131 kurulumlarda yap\u0131lmas\u0131 gerekti\u011fini belirtir.<\/p>\n<h2><span style=\"font-size: 12pt;\">DOP Fakt\u00f6r\u00fc<\/span><\/h2>\n<p>DOP fotometre testinden sonra, DOP&#8217;un filtreden tekrar tamamen serbest b\u0131rak\u0131lmas\u0131 genellikle birka\u00e7 ay al\u0131r. \u00d6zellikle temiz oda i\u015fletimi ba\u015flarken hassas \u00fcr\u00fcnlerin k\u0131sa s\u00fcreli y\u00fcksek seviyede kontaminasyonu dikkate al\u0131nmal\u0131d\u0131r. Optik partik\u00fcl sayac\u0131 \u00f6l\u00e7\u00fcmleri \u00e7ok k\u00fc\u00e7\u00fck partik\u00fcl konsantrasyonlar\u0131na daha duyarl\u0131 oldu\u011fundan ve partik\u00fcl say\u0131s\u0131 da\u011f\u0131l\u0131mlar\u0131n\u0131n bu tek partik\u00fcl analiziyle g\u00f6zlemlenmesi durumunda k\u00fc\u00e7\u00fck partik\u00fcller bask\u0131n oldu\u011fundan, optik partik\u00fcl sayac\u0131 \u00f6l\u00e7\u00fcmleri bir fotometre testine k\u0131yasla k\u00fc\u00e7\u00fck s\u0131z\u0131nt\u0131lar\u0131 tespit etmek i\u00e7in \u00e7ok daha hassast\u0131r.<\/p>\n<h2><span style=\"font-size: 12pt;\">Kar\u015f\u0131la\u015ft\u0131rma Tablosu<\/span><\/h2>\n<table width=\"604\">\n<tbody>\n<tr>\n<td width=\"113\">\n<p><strong>\u00a0<\/strong><\/p>\n<\/td>\n<td width=\"255\">\n<p><strong>Optik Partik\u00fcl Say\u0131c\u0131<\/strong><\/p>\n<\/td>\n<td width=\"236\">\n<p><strong>Fotometre<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"113\">\n<p><strong>\u00d6l\u00e7\u00fcm Prensibi<\/strong><\/p>\n<\/td>\n<td width=\"255\">\n<p>\u00b7 I\u015f\u0131k sa\u00e7\u0131l\u0131m\u0131<\/p>\n<p>\u00b7 Tek partik\u00fcl analiz<\/p>\n<p>\u00b7 Mutlak \u00d6l\u00e7\u00fcm metodu<br \/>(ayr\u0131k konsantrasyon \u00f6l\u00e7\u00fcm\u00fc \u2013upstream ve down stream)<\/p>\n<\/td>\n<td width=\"236\">\n<p>\u00b7 I\u015f\u0131k Transmisyonu (veya \u0131\u015f\u0131k sa\u00e7\u0131l\u0131m\u0131n\u0131n iletimi)<\/p>\n<p>\u00b7 Partik\u00fcl toplama analizi<\/p>\n<p>\u00b7 Relatif \u00f6l\u00e7\u00fcm metodu (konsantrasyon oranl\u0131 \u00f6l\u00e7\u00fcm)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"113\">\n<p><strong>\u00d6l\u00e7\u00fcm Konsantrasyonu<\/strong><\/p>\n<\/td>\n<td width=\"255\">\n<p>\u00b7 Partik\u00fcl say\u0131m konsantrasyonu<\/p>\n<p>\u00b7 K\u00fc\u00e7\u00fck partik\u00fcllerin g\u00fc\u00e7l\u00fc etkisi<\/p>\n<\/td>\n<td width=\"236\">\n<p>\u00b7 Partik\u00fcl k\u00fctle konsantrasyonu<\/p>\n<p>\u00b7 B\u00fcy\u00fck partik\u00fcllerde g\u00fc\u00e7l\u00fc etki<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"113\">\n<p><strong>Partik\u00fcl boyut bilgisi<\/strong><\/p>\n<\/td>\n<td width=\"255\">\n<p>\u00b7 Ayr\u0131k partik\u00fcl boyut \u00e7\u00f6z\u00fcn\u00fcrl\u00fc\u011f\u00fc<\/p>\n<\/td>\n<td width=\"236\">\n<p>Ortalama partik\u00fcl boyutu, partik\u00fcl boyut \u00e7\u00f6z\u00fcn\u00fcrl\u00fc\u00fc\u011f yok<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"113\">\n<p><strong>Avantajlar<\/strong><\/p>\n<\/td>\n<td width=\"255\">\n<p>\u00b7 Filtre kontaminasyonu yok<\/p>\n<p>\u00b7 K\u00fc\u00e7\u00fck ka\u00e7aklar\u0131n deteksiyonu<\/p>\n<p>\u00b7 K\u0131sa entegrasyon aral\u0131klar\u0131, h\u0131zl\u0131 tarama i\u00e7in y\u00fcksek uzaysal \u00e7\u00f6z\u00fcn\u00fcrl\u00fck<\/p>\n<\/td>\n<td width=\"236\">\n<p>Upstream dil\u00fctasyona gerek yok<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td width=\"113\">\n<p><strong>K\u0131s\u0131tlamalar<\/strong><\/p>\n<\/td>\n<td width=\"255\">\n<p>\u00b7 Upstream dilasyon co-insidans hatalar\u0131ndan ka\u00e7\u0131nmay\u0131 gerektirir<\/p>\n<\/td>\n<td width=\"236\">\n<p>\u00b7 Filtre kontaminasyonu (y\u00fcksek upstream konsantrasyonlarda)<\/p>\n<p>\u00b7 K\u00fc\u00e7\u00fck partik\u00fcllerin deteksiyonunda d\u00fc\u015f\u00fck duyarl\u0131l\u0131k<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2><strong><br \/><\/strong><span style=\"font-size: 14pt;\"><strong>\u00d6zetle<\/strong> :<\/span><\/h2>\n<p>Yukar\u0131da tart\u0131\u015f\u0131lan farkl\u0131 y\u00f6nlerin bir sonucu olarak, <span style=\"font-size: 12pt;\">Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 sonucunda,\u00a0<\/span>tak\u0131l\u0131 filtre ka\u00e7ak testlerini ger\u00e7ekle\u015ftirmek i\u00e7in diluter kullan\u0131larak bir optik partik\u00fcl sayac\u0131n\u0131n uygulanmas\u0131 \u015fiddetle tavsiye edilir.<\/p>\n<p><strong><em><br \/>Kaynak : <a href=\"https:\/\/www.topas-gmbh.de\/\" target=\"_blank\" rel=\"noopener noreferrer\">Topas GmbH<\/a><\/em><\/strong><\/p>\n<figure id=\"attachment_3144\" aria-describedby=\"caption-attachment-3144\" style=\"width: 300px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-3144 size-full\" src=\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2020\/06\/topas-logo.png\" alt=\"Topas GMBH\" width=\"300\" height=\"128\" \/><figcaption id=\"caption-attachment-3144\" class=\"wp-caption-text\">Topas GMBH<\/figcaption><\/figure>\n<p>Topas di\u011fer \u00fcr\u00fcnler i\u00e7in -&gt; <a href=\"https:\/\/www.medibim.com.tr\/TR\/topas\/\">t\u0131klay\u0131n\u0131z.<\/a><\/p>\n<p>Topas Temiz Oda validasyon ekipmanlar\u0131 i\u00e7in ve detayl\u0131 bilgi i\u00e7in l\u00fctfen bizimle ileti\u015fime ge\u00e7iniz.<\/p>\n<p>Medibim<br \/>0212.4382046 \/ 47<br \/>info@medibim.com.tr<br \/>Topas T\u00fcrkiye<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 [rml_read_more] Hepa filtre ka\u00e7ak testi ISO 14644 standart\u0131na g\u00f6re 2 farkl\u0131 y\u00f6ntemle yap\u0131lmaktad\u0131r.<\/p>\n","protected":false},"author":18,"featured_media":2001,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"colormag_page_container_layout":"default_layout","colormag_page_sidebar_layout":"default_layout","footnotes":""},"categories":[881,38,1210],"tags":[839,1222,1221,1219,923,924,1223,1224,827,1217],"class_list":["post-3129","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-literatur","category-temiz-oda-validasyon-ekipmanlari","category-topas","tag-dop-testi","tag-dpc-opc-fotometre","tag-dpc-yontemi","tag-fotometre-testi","tag-hepa-filtre-kacak-testi","tag-integrity-test","tag-opc-fotometre","tag-opc-fotometre-karsilastirma","tag-topas","tag-upstream-test"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.1.1 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon<\/title>\n<meta name=\"description\" content=\"Temiz Oda Validasyon Ekipmanlar\u0131 - Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/\" \/>\n<meta property=\"og:locale\" content=\"tr_TR\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon\" \/>\n<meta property=\"og:description\" content=\"Temiz Oda Validasyon Ekipmanlar\u0131 - Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/\" \/>\n<meta property=\"og:site_name\" content=\"Medibim Biyomedikal Metroloji ve Kalibrasyon\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/medibim\" \/>\n<meta property=\"article:published_time\" content=\"2020-06-15T17:42:08+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2025-04-18T08:06:26+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"800\" \/>\n\t<meta property=\"og:image:height\" content=\"444\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"medibim\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@medibim\" \/>\n<meta name=\"twitter:site\" content=\"@medibim\" \/>\n<meta name=\"twitter:label1\" content=\"Yazan:\" \/>\n\t<meta name=\"twitter:data1\" content=\"medibim\" \/>\n\t<meta name=\"twitter:label2\" content=\"Tahmini okuma s\u00fcresi\" \/>\n\t<meta name=\"twitter:data2\" content=\"9 dakika\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/\"},\"author\":{\"name\":\"medibim\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/person\/a4ff9d43f488c54da9fe049edfeb40d4\"},\"headline\":\"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131\",\"datePublished\":\"2020-06-15T17:42:08+00:00\",\"dateModified\":\"2025-04-18T08:06:26+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/\"},\"wordCount\":1925,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#organization\"},\"image\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg\",\"keywords\":[\"DOP testi\",\"DPC OPC Fotometre\",\"dpc y\u00f6ntemi\",\"fotometre testi\",\"hepa filtre ka\u00e7ak testi\",\"integrity test\",\"OPC Fotometre\",\"OPC Fotometre kar\u015f\u0131la\u015ft\u0131rma\",\"topas\",\"upstream test\"],\"articleSection\":[\"Literat\u00fcr\",\"Temiz Oda Validasyon Ekipmanlar\u0131\",\"Topas\"],\"inLanguage\":\"tr\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/\",\"url\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/\",\"name\":\"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon\",\"isPartOf\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg\",\"datePublished\":\"2020-06-15T17:42:08+00:00\",\"dateModified\":\"2025-04-18T08:06:26+00:00\",\"description\":\"Temiz Oda Validasyon Ekipmanlar\u0131 - Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon\",\"breadcrumb\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#breadcrumb\"},\"inLanguage\":\"tr\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"tr\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#primaryimage\",\"url\":\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg\",\"contentUrl\":\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg\",\"width\":800,\"height\":444,\"caption\":\"Hepa filtre S\u0131zd\u0131rmazl\u0131k Ka\u00e7ak DOP Testi\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Ana sayfa\",\"item\":\"https:\/\/www.medibim.com.tr\/TR\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#website\",\"url\":\"https:\/\/www.medibim.com.tr\/TR\/\",\"name\":\"Medibim Biyomedikal Metroloji ve Kalibrasyon\",\"description\":\"Test Muayene Kalibrasyon Validasyon Kalibrat\u00f6r E\u011fitim\",\"publisher\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/www.medibim.com.tr\/TR\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"tr\"},{\"@type\":\"Organization\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#organization\",\"name\":\"Medibim Biyomedikal\",\"alternateName\":\"Biyomedikal Metroloji ve Kalibrasyon Hizmetleri\",\"url\":\"https:\/\/www.medibim.com.tr\/TR\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"tr\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/logo\/image\/\",\"url\":\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/10\/medibim-logo-150x72-72dpi.png\",\"contentUrl\":\"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/10\/medibim-logo-150x72-72dpi.png\",\"width\":150,\"height\":72,\"caption\":\"Medibim Biyomedikal\"},\"image\":{\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/logo\/image\/\"},\"sameAs\":[\"https:\/\/www.facebook.com\/medibim\",\"https:\/\/x.com\/medibim\",\"https:\/\/www.linkedin.com\/in\/medibim-biyomedikal-metroloji-bb952059\/\",\"https:\/\/www.facebook.com\/medibim-biyomedikal\"]},{\"@type\":\"Person\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/person\/a4ff9d43f488c54da9fe049edfeb40d4\",\"name\":\"medibim\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"tr\",\"@id\":\"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/secure.gravatar.com\/avatar\/1fc9c03014482fd7ddcbbd5f7b6deca9e040ed6690a2fed9fa182dbe8ef7280b?s=96&d=mm&r=g\",\"contentUrl\":\"https:\/\/secure.gravatar.com\/avatar\/1fc9c03014482fd7ddcbbd5f7b6deca9e040ed6690a2fed9fa182dbe8ef7280b?s=96&d=mm&r=g\",\"caption\":\"medibim\"},\"url\":\"https:\/\/www.medibim.com.tr\/TR\/author\/medibim\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon","description":"Temiz Oda Validasyon Ekipmanlar\u0131 - Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/","og_locale":"tr_TR","og_type":"article","og_title":"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon","og_description":"Temiz Oda Validasyon Ekipmanlar\u0131 - Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon","og_url":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/","og_site_name":"Medibim Biyomedikal Metroloji ve Kalibrasyon","article_publisher":"https:\/\/www.facebook.com\/medibim","article_published_time":"2020-06-15T17:42:08+00:00","article_modified_time":"2025-04-18T08:06:26+00:00","og_image":[{"width":800,"height":444,"url":"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg","type":"image\/jpeg"}],"author":"medibim","twitter_card":"summary_large_image","twitter_creator":"@medibim","twitter_site":"@medibim","twitter_misc":{"Yazan:":"medibim","Tahmini okuma s\u00fcresi":"9 dakika"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#article","isPartOf":{"@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/"},"author":{"name":"medibim","@id":"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/person\/a4ff9d43f488c54da9fe049edfeb40d4"},"headline":"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131","datePublished":"2020-06-15T17:42:08+00:00","dateModified":"2025-04-18T08:06:26+00:00","mainEntityOfPage":{"@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/"},"wordCount":1925,"commentCount":0,"publisher":{"@id":"https:\/\/www.medibim.com.tr\/TR\/#organization"},"image":{"@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#primaryimage"},"thumbnailUrl":"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg","keywords":["DOP testi","DPC OPC Fotometre","dpc y\u00f6ntemi","fotometre testi","hepa filtre ka\u00e7ak testi","integrity test","OPC Fotometre","OPC Fotometre kar\u015f\u0131la\u015ft\u0131rma","topas","upstream test"],"articleSection":["Literat\u00fcr","Temiz Oda Validasyon Ekipmanlar\u0131","Topas"],"inLanguage":"tr","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/","url":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/","name":"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon","isPartOf":{"@id":"https:\/\/www.medibim.com.tr\/TR\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#primaryimage"},"image":{"@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#primaryimage"},"thumbnailUrl":"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg","datePublished":"2020-06-15T17:42:08+00:00","dateModified":"2025-04-18T08:06:26+00:00","description":"Temiz Oda Validasyon Ekipmanlar\u0131 - Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131 - Medibim Biyomedikal Metroloji ve Kalibrasyon","breadcrumb":{"@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#breadcrumb"},"inLanguage":"tr","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/"]}]},{"@type":"ImageObject","inLanguage":"tr","@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#primaryimage","url":"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg","contentUrl":"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/11\/hepa-1.jpg","width":800,"height":444,"caption":"Hepa filtre S\u0131zd\u0131rmazl\u0131k Ka\u00e7ak DOP Testi"},{"@type":"BreadcrumbList","@id":"https:\/\/www.medibim.com.tr\/TR\/temiz-oda-validasyon-ekipmanlari\/hepa-kacak-testinde-partikul-sayici-fotometre-karsilastirmasi\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Ana sayfa","item":"https:\/\/www.medibim.com.tr\/TR\/"},{"@type":"ListItem","position":2,"name":"Hepa Ka\u00e7ak Testinde Partik\u00fcl Say\u0131c\u0131 Fotometre Kar\u015f\u0131la\u015ft\u0131rmas\u0131"}]},{"@type":"WebSite","@id":"https:\/\/www.medibim.com.tr\/TR\/#website","url":"https:\/\/www.medibim.com.tr\/TR\/","name":"Medibim Biyomedikal Metroloji ve Kalibrasyon","description":"Test Muayene Kalibrasyon Validasyon Kalibrat\u00f6r E\u011fitim","publisher":{"@id":"https:\/\/www.medibim.com.tr\/TR\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.medibim.com.tr\/TR\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"tr"},{"@type":"Organization","@id":"https:\/\/www.medibim.com.tr\/TR\/#organization","name":"Medibim Biyomedikal","alternateName":"Biyomedikal Metroloji ve Kalibrasyon Hizmetleri","url":"https:\/\/www.medibim.com.tr\/TR\/","logo":{"@type":"ImageObject","inLanguage":"tr","@id":"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/logo\/image\/","url":"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/10\/medibim-logo-150x72-72dpi.png","contentUrl":"https:\/\/www.medibim.com.tr\/TR\/wp-content\/uploads\/2018\/10\/medibim-logo-150x72-72dpi.png","width":150,"height":72,"caption":"Medibim Biyomedikal"},"image":{"@id":"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/www.facebook.com\/medibim","https:\/\/x.com\/medibim","https:\/\/www.linkedin.com\/in\/medibim-biyomedikal-metroloji-bb952059\/","https:\/\/www.facebook.com\/medibim-biyomedikal"]},{"@type":"Person","@id":"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/person\/a4ff9d43f488c54da9fe049edfeb40d4","name":"medibim","image":{"@type":"ImageObject","inLanguage":"tr","@id":"https:\/\/www.medibim.com.tr\/TR\/#\/schema\/person\/image\/","url":"https:\/\/secure.gravatar.com\/avatar\/1fc9c03014482fd7ddcbbd5f7b6deca9e040ed6690a2fed9fa182dbe8ef7280b?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/1fc9c03014482fd7ddcbbd5f7b6deca9e040ed6690a2fed9fa182dbe8ef7280b?s=96&d=mm&r=g","caption":"medibim"},"url":"https:\/\/www.medibim.com.tr\/TR\/author\/medibim\/"}]}},"_links":{"self":[{"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/posts\/3129","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/users\/18"}],"replies":[{"embeddable":true,"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/comments?post=3129"}],"version-history":[{"count":17,"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/posts\/3129\/revisions"}],"predecessor-version":[{"id":4027,"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/posts\/3129\/revisions\/4027"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/media\/2001"}],"wp:attachment":[{"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/media?parent=3129"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/categories?post=3129"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.medibim.com.tr\/TR\/wp-json\/wp\/v2\/tags?post=3129"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}